Wire size calculator:
by current and voltage drop

Type the current, one-way length, voltage and the drop you allow, and get the smallest wire size that carries the current and keeps the voltage drop in limits.

ft
A
V
%
Smallest wire that works8 AWG1.91% drop (2.29 V) · rated 50 A
Needed for the voltage drop
8 AWG
Needed for the current (NEC 75 °C)
14 AWG
Current used for sizing
15 A
SizeDropDrop %AmpacityOK
14 AWG9.21 V7.68%15 ANo
12 AWG5.79 V4.83%20 ANo
10 AWG3.64 V3.04%30 ANo
8 AWG2.29 V1.91%50 AYes
6 AWG1.44 V1.2%65 AYes
4 AWG0.91 V0.76%85 AYes
3 AWG0.72 V0.6%100 AYes
2 AWG0.57 V0.48%115 AYes
1 AWG0.45 V0.38%130 AYes
1/0 AWG0.36 V0.3%150 AYes
2/0 AWG0.28 V0.24%175 AYes
3/0 AWG0.23 V0.19%200 AYes
4/0 AWG0.18 V0.15%230 AYes
250 kcmil0.15 V0.13%255 AYes
  • Ampacity from NEC Table 310.16 (75 °C terminals, not more than three current-carrying conductors, 30 °C ambient) with the 240.4(D) limits for small wire. Hot attics, bundling or 60 °C devices lower it.

How to use Wire size calculator

  1. 01Type the loadAmps, volts, phase.
  2. 02Add the runOne-way length.
  3. 03Read the sizeWith each size compared.
File character arranging marked pages

Two tests, the bigger wins.

For AWG sizes each wire is checked against NEC Table 310.16 (75 °C column, with the small-conductor limits) and against your voltage-drop limit; the answer is the first size that passes both. For mm² the voltage-drop test is done and you check the current rating in your national tables.

At a glance

Price
Free. No sign-up, no watermark.
Privacy
Your text stays in your browser. Nothing is uploaded.
Works in
Chrome, Edge, Firefox and Safari, on phones and computers

Questions

What size wire for 40 amps?

For a short run, 8 AWG copper (50 A at 75 °C) is the usual answer, or 6 AWG aluminium. On a long run the voltage drop may call for one size bigger.

What size wire for 15 A at 100 ft?

At 120 V, 14 AWG is rated for 15 A, but over 100 ft the drop is 7.7%. 12 AWG gives 4.8%, 10 AWG 3.6% and 8 AWG 2.3%, so 8 AWG is needed for a 3% limit (10 AWG for 5%).

What is the 125% rule?

Loads that run for three hours or more, like EV chargers and water heaters, are sized at 125% of their current. Tick “continuous load” to apply it.

Is what I type sent anywhere?

No. The calculation runs in your browser and nothing you type leaves your device.