How to use Voltage drop calculator
- 01Choose the wireMaterial and size.
- 02Type the circuitLength, amps, volts, phase.
- 03Read the dropVolts, percent, watts lost.

Resistance × current × length.
The wire’s resistance per metre comes from its area and the resistivity of copper (0.017241 Ω·mm²/m at 20 °C) or aluminium (0.028264), corrected for temperature. Single-phase and DC drop is 2 × length × current × resistance (out and back); three phase uses √3 instead of 2.
At a glance
- Price
- Free. No sign-up, no watermark.
- Privacy
- Your text stays in your browser. Nothing is uploaded.
- Works in
- Chrome, Edge, Firefox and Safari, on phones and computers
Questions
What is the voltage drop of 12 AWG over 100 ft at 15 A?
At 75 °C, 12 AWG copper is about 1.93 Ω per 1,000 ft. Out and back is 200 ft, so 0.2 × 1.93 × 15 = 5.8 V, which is 4.8% of 120 V: too much for a branch circuit. 8 AWG brings it to about 2.3%.
How much voltage drop is allowed?
The NEC recommends no more than 3% on a branch circuit and 5% for feeder and branch together. IEC 60364 gives 3% for lighting and 5% for other loads on a public supply.
What does 7/29 mean?
It is a stranded cable of 7 wires each 0.029 in thick, a naming used in Pakistan and India. 7/29 has about 2.98 mm² of copper, close to a 2.5 mm² cable; 7/36 is about 4.6 mm².
Is what I type sent anywhere?
No. The calculation runs in your browser and nothing you type leaves your device.