How to use UPS and inverter battery backup calculator
- 01Choose the batteryType, Ah and volts.
- 02Type the loadWatts running on backup.
- 03Read the backupOr the battery you need.

Stored energy ÷ load.
A battery stores Ah × V watt-hours. Only part of that should be used: about 50% for lead-acid and tubular batteries, 80–90% for lithium (LiFePO4). The inverter loses 10–15% turning it into AC. What remains, divided by your load in watts, is the hours of backup.
At a glance
- Price
- Free. No sign-up, no watermark.
- Privacy
- Your text stays in your browser. Nothing is uploaded.
- Works in
- Chrome, Edge, Firefox and Safari, on phones and computers
Questions
How long will a 150 Ah battery last on 300 W?
150 × 12 = 1,800 Wh. Using half of it (lead-acid) gives 900 Wh, and after an 85% efficient inverter 765 Wh. 765 ÷ 300 = 2.55 hours, about 2 h 33 min.
What battery do I need for 4 hours of 300 W?
300 × 4 = 1,200 Wh at the load ÷ 0.5 ÷ 0.85 = 2,824 Wh of battery, or 235 Ah at 12 V: two 150 Ah lead-acid batteries. With lithium (90% usable) it is 1,569 Wh, so one 150 Ah battery.
What UPS size do I need?
At least the load ÷ 0.8 in VA: 300 W needs a 375 VA or larger UPS. Motors and pumps need more for their starting surge.
Is what I type sent anywhere?
No. The calculation runs in your browser and nothing you type leaves your device.